Home Search Emissions Pollutants About the Database


Phillips 66 (2418), Belle Chasse

LDEQ Accident Report

Accident #119864
State Police #09-06572
Accident Date2009-12-05
Report Date 2009-12-09
Follow-up Date 0000-00-00
Follow-up: No

Pollutants Released

Pollutant Duration Point Source Greenhouse Gas Criteria Pollutant Ozone forming chemical Amount of Release
Sulfur Dioxide12h 28mNo information givenNOYESNO241.0 pounds
YESYESYES 
YESYESYES 
YESYESYES 
YESYESYES 

Accident Classified As:

Cause of Problem: Process Upset

The 592 Sulfur Recovery Unit (SRU) has 3 combustion air blowers. Usually, 2 are on line. On 12/5, one of the two operating blowers tripped due to a thermal overload. This drop in air discharge pressure activated the Low Combustion Air Pressure alarm which shutdown combustion in the SRU Reaction Furnace. This activated the Sour Water Stripper (SWS).

Discharge Preventable - No Information Given

No Information Given

Notes/Remedial Actions

The refinery initiated "sulfur-shedding" procedures until SRU could be brought back online.