Home Search Emissions Pollutants About the Database


Motiva Enterprises (1406), Norco

LDEQ Accident Report

Accident #153594
State Police #14-00473
Accident Date2014-01-28
Report Date 2014-02-04
Follow-up Date 0000-00-00
Follow-up: No

Pollutants Released

Pollutant Duration Point Source Greenhouse Gas Criteria Pollutant Ozone forming chemical Amount of Release
Propylene54mRelief Valve @ Residual Cat. Cracking UnitNONOYES 

Accident Classified As: No Information Given

Cause of Problem: Equipment Failure

Relief valve on the depropanizer column at the Residual Catalytic Cracking Unit had lifted. Due to the inclement weather conditions, the pilot tubing for the Relief Valve was frozen which caused the Relief Valve inlet block valve to remain closed resulting in the relief valve to fail in the open position.

Discharge Preventable - No Information Given

Notes/Remedial Actions