Accident # | 96958 |
State Police # | 07-1938 |
Accident Date | 2007-06-10 |
Report Date | 2007-06-10 |
Follow-up Date | 2007-06-15 |
Follow-up: | Yes |
Pollutant | Duration | Point Source | Greenhouse Gas | Criteria Pollutant | Ozone forming chemical | Amount of Release |
Flammable Gas | 17m | relief valve at RCCU | NO | NO | YES | 85,445.0 pounds |
Volatile Organic Compounds (VOCs) | 17m | relief valve at RCCU | NO | NO | YES | 85,445.0 pounds |
Highly Reactive Volatile Organic Compounds (HRVOCs) | NO | NO | NO | 64,091.0 |
Accident Classified As: Reportable Quantity
Depropanizer column relief valve (RV-7207) failed at the Residual Catalytic Cracking Unit, prematurely relieving below its set pressure.
Not preventable due to the fact that RV-7207 was properly maintained and has met all inspection criteria.
Valve was isolated to stop release, "employed proper mitigation steps for alternate relief protection to prevent further environmental impact," valve removed, sent off for repair and reinstalled. It was noted that there was a noise associated with the RV piping at the time of the release--one complaint received.