Home Search Emissions Pollutants About the Database


Alon Refining (3116), Krotz Springs

Releases in 2010

LDEQ Accident Number
Accident Date
Point Source/Release CauseNotes
127252

2010-10-25
Point Source(s):
FLARE - FCCU flare

Pollutant(s):
Sulfur Dioxide - 111 pounds
Hydrogen Sulfide - 3 pounds
Nitric Oxide - 15 pounds
Volatile Organic Compounds (VOCs) - 663 pounds
Carbon Monoxide - 110 pounds
1,3-Butadiene - 4 pounds
n-Hexane - 32 pounds
Nitrogen Dioxide - 2 pounds
Cause of Problem: Power Failure

"Loss of power in Complex II caused operating and utility units to shutdown. This even resulted in flaring from the FCCU flare" Due to the loss of power, the complex II steam producers shut down, therefore the flare steam assist was lost. This resulted in smoking flares. This released the following chemicals: SO2, H2S, NOx, VOC, Hexane, and 1,3 Butadiene. FLARE.
A power feed was connected from Complex I to Complex II, and boilers were restarted to produce steam to assist the FCCU flare, and shutdown procedures was continued. No LDEQ report. Refinery Letter only.